Voltage Drop Calculator

HomeWire sizeWire gauge

2 AWG wire

2 AWG copper carries 115 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

2 AWG specifications

PropertyValue
Diameter, solid0.2576 in (6.54 mm)
Area66,360 cmil (33.62 mm²)
Resistance, copper0.194 Ω per 1,000 ft
Resistance, aluminum0.319 Ω per 1,000 ft
Copper ampacity95 / 115 / 130 A at 60 / 75 / 90 °C
Aluminum ampacity75 / 90 / 100 A
Largest breaker110 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 2 AWG can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
28 A662 ft1,104 ft
55 A337 ft562 ft
88 A210 ft351 ft
110 A168 ft281 ft

Copper, single-phase.

What 2 AWG is used for

2 AWG copper is the usual choice for 100 to 115 A feeders and services. In NM-B cable it is limited to the 60 °C rating, 95 A. Neighboring sizes: 3 AWG, 1 AWG.

Common questions

How many amps can 2 AWG carry?

95 A at 60 °C, 115 A at 75 °C and 130 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 2 AWG?

0.2576 in (6.54 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)