3 AWG wire
3 AWG copper carries 100 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
3 AWG specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.2294 in (5.83 mm) |
| Area | 52,620 cmil (26.66 mm²) |
| Resistance, copper | 0.245 Ω per 1,000 ft |
| Resistance, aluminum | 0.403 Ω per 1,000 ft |
| Copper ampacity | 85 / 100 / 115 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 65 / 75 / 85 A |
| Largest breaker | 100 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 3 AWG can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 25 A | 587 ft | 979 ft |
| 50 A | 293 ft | 489 ft |
| 80 A | 183 ft | 306 ft |
| 100 A | 146 ft | 244 ft |
Copper, single-phase.
Common questions
How many amps can 3 AWG carry?
85 A at 60 °C, 100 A at 75 °C and 115 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 3 AWG?
0.2294 in (5.83 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)