4 AWG wire
4 AWG copper carries 85 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
4 AWG specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.2043 in (5.19 mm) |
| Area | 41,740 cmil (21.15 mm²) |
| Resistance, copper | 0.308 Ω per 1,000 ft |
| Resistance, aluminum | 0.508 Ω per 1,000 ft |
| Copper ampacity | 70 / 85 / 95 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 55 / 65 / 75 A |
| Largest breaker | 80 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 4 AWG can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 20 A | 584 ft | 974 ft |
| 40 A | 292 ft | 487 ft |
| 64 A | 182 ft | 304 ft |
| 80 A | 146 ft | 243 ft |
Copper, single-phase.
Common questions
How many amps can 4 AWG carry?
70 A at 60 °C, 85 A at 75 °C and 95 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 4 AWG?
0.2043 in (5.19 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)