Voltage Drop Calculator

HomeWire sizeWire gauge

4 AWG wire

4 AWG copper carries 85 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

4 AWG specifications

PropertyValue
Diameter, solid0.2043 in (5.19 mm)
Area41,740 cmil (21.15 mm²)
Resistance, copper0.308 Ω per 1,000 ft
Resistance, aluminum0.508 Ω per 1,000 ft
Copper ampacity70 / 85 / 95 A at 60 / 75 / 90 °C
Aluminum ampacity55 / 65 / 75 A
Largest breaker80 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 4 AWG can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
20 A584 ft974 ft
40 A292 ft487 ft
64 A182 ft304 ft
80 A146 ft243 ft

Copper, single-phase.

What 4 AWG is used for

4 AWG copper is the usual choice for 70 to 85 A subpanels and 100 A aluminum-equivalent feeders. In NM-B cable it is limited to the 60 °C rating, 70 A. Neighboring sizes: 6 AWG, 3 AWG.

Common questions

How many amps can 4 AWG carry?

70 A at 60 °C, 85 A at 75 °C and 95 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 4 AWG?

0.2043 in (5.19 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)