6 AWG wire
6 AWG copper carries 65 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
6 AWG specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.1620 in (4.11 mm) |
| Area | 26,240 cmil (13.30 mm²) |
| Resistance, copper | 0.491 Ω per 1,000 ft |
| Resistance, aluminum | 0.808 Ω per 1,000 ft |
| Copper ampacity | 55 / 65 / 75 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 40 / 50 / 55 A |
| Largest breaker | 60 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 6 AWG can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 15 A | 488 ft | 814 ft |
| 30 A | 244 ft | 407 ft |
| 48 A | 152 ft | 254 ft |
| 60 A | 122 ft | 203 ft |
Copper, single-phase.
Common questions
How many amps can 6 AWG carry?
55 A at 60 °C, 65 A at 75 °C and 75 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 6 AWG?
0.1620 in (4.11 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)