8 AWG wire
8 AWG copper carries 50 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
8 AWG specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.1285 in (3.26 mm) |
| Area | 16,510 cmil (8.37 mm²) |
| Resistance, copper | 0.778 Ω per 1,000 ft |
| Resistance, aluminum | 1.28 Ω per 1,000 ft |
| Copper ampacity | 40 / 50 / 55 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 35 / 40 / 45 A |
| Largest breaker | 50 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 8 AWG can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 12 A | 385 ft | 642 ft |
| 25 A | 185 ft | 308 ft |
| 40 A | 115 ft | 192 ft |
| 50 A | 92 ft | 154 ft |
Copper, single-phase.
Common questions
How many amps can 8 AWG carry?
40 A at 60 °C, 50 A at 75 °C and 55 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 8 AWG?
0.1285 in (3.26 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.