8 AWG wire

8 AWG copper carries 50 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

8 AWG specifications

PropertyValue
Diameter, solid0.1285 in (3.26 mm)
Area16,510 cmil (8.37 mm²)
Resistance, copper0.778 Ω per 1,000 ft
Resistance, aluminum1.28 Ω per 1,000 ft
Copper ampacity40 / 50 / 55 A at 60 / 75 / 90 °C
Aluminum ampacity35 / 40 / 45 A
Largest breaker50 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 8 AWG can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
12 A385 ft642 ft
25 A185 ft308 ft
40 A115 ft192 ft
50 A92 ft154 ft

Copper, single-phase.

What 8 AWG is used for

8 AWG copper is the usual choice for 40 to 50 A ranges, cooktops and EV chargers. In NM-B cable it is limited to the 60 °C rating, 40 A. Neighboring sizes: 10 AWG, 6 AWG.

Common questions

How many amps can 8 AWG carry?

40 A at 60 °C, 50 A at 75 °C and 55 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 8 AWG?

0.1285 in (3.26 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.