10 AWG wire
10 AWG copper carries 35 A at 75 °C, limited to a 30 A breaker. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
10 AWG specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.1019 in (2.59 mm) |
| Area | 10,380 cmil (5.26 mm²) |
| Resistance, copper | 1.24 Ω per 1,000 ft |
| Resistance, aluminum | 2.04 Ω per 1,000 ft |
| Copper ampacity | 30 / 35 / 40 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 25 / 30 / 35 A |
| Largest breaker | 30 A (240.4(D)) |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 10 AWG can run
One-way distance at 3% and 5% drop.
| Load | 120 V, 3% | 240 V, 3% | 120 V, 5% | 240 V, 5% |
|---|---|---|---|---|
| 8 A | 181 ft | 362 ft | 302 ft | 604 ft |
| 15 A | 96 ft | 193 ft | 161 ft | 322 ft |
| 24 A | 60 ft | 120 ft | 100 ft | 201 ft |
| 30 A | 48 ft | 96 ft | 80 ft | 161 ft |
Copper, single-phase.
Common questions
How many amps can 10 AWG carry?
30 A at 60 °C, 35 A at 75 °C and 40 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C. The breaker is still limited to 30 A by 240.4(D).
What is the diameter of 10 AWG?
0.1019 in (2.59 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)