Voltage Drop Calculator

HomeWire sizeWire gauge

10 AWG wire

10 AWG copper carries 35 A at 75 °C, limited to a 30 A breaker. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

10 AWG specifications

PropertyValue
Diameter, solid0.1019 in (2.59 mm)
Area10,380 cmil (5.26 mm²)
Resistance, copper1.24 Ω per 1,000 ft
Resistance, aluminum2.04 Ω per 1,000 ft
Copper ampacity30 / 35 / 40 A at 60 / 75 / 90 °C
Aluminum ampacity25 / 30 / 35 A
Largest breaker30 A (240.4(D))

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 10 AWG can run

One-way distance at 3% and 5% drop.

Load120 V, 3%240 V, 3%120 V, 5%240 V, 5%
8 A181 ft362 ft302 ft604 ft
15 A96 ft193 ft161 ft322 ft
24 A60 ft120 ft100 ft201 ft
30 A48 ft96 ft80 ft161 ft

Copper, single-phase.

What 10 AWG is used for

10 AWG copper is the usual choice for 30 A dryers, water heaters and small AC units. In NM-B cable it is limited to the 60 °C rating, 30 A. Neighboring sizes: 12 AWG, 8 AWG.

Common questions

How many amps can 10 AWG carry?

30 A at 60 °C, 35 A at 75 °C and 40 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C. The breaker is still limited to 30 A by 240.4(D).

What is the diameter of 10 AWG?

0.1019 in (2.59 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)