Voltage Drop Calculator

HomeWire sizeWire gauge

12 AWG wire

12 AWG copper carries 25 A at 75 °C, limited to a 20 A breaker. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

12 AWG specifications

PropertyValue
Diameter, solid0.0808 in (2.05 mm)
Area6,530 cmil (3.31 mm²)
Resistance, copper1.98 Ω per 1,000 ft
Resistance, aluminum3.25 Ω per 1,000 ft
Copper ampacity20 / 25 / 30 A at 60 / 75 / 90 °C
Aluminum ampacity15 / 20 / 25 A
Largest breaker20 A (240.4(D))

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 12 AWG can run

One-way distance at 3% and 5% drop.

Load120 V, 3%240 V, 3%120 V, 5%240 V, 5%
5 A181 ft363 ft303 ft606 ft
10 A90 ft181 ft151 ft303 ft
16 A56 ft113 ft94 ft189 ft
20 A45 ft90 ft75 ft151 ft

Copper, single-phase.

What 12 AWG is used for

12 AWG copper is the usual choice for 20 A kitchen, bath, laundry and garage circuits. In NM-B cable it is limited to the 60 °C rating, 20 A. Neighboring sizes: 14 AWG, 10 AWG.

Common questions

How many amps can 12 AWG carry?

20 A at 60 °C, 25 A at 75 °C and 30 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C. The breaker is still limited to 20 A by 240.4(D).

What is the diameter of 12 AWG?

0.0808 in (2.05 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)