Voltage Drop Calculator

HomeWire sizeWire gauge

14 AWG wire

14 AWG copper carries 20 A at 75 °C, limited to a 15 A breaker. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

14 AWG specifications

PropertyValue
Diameter, solid0.0641 in (1.63 mm)
Area4,110 cmil (2.08 mm²)
Resistance, copper3.14 Ω per 1,000 ft
Resistance, aluminumnot made in aluminum
Copper ampacity15 / 20 / 25 A at 60 / 75 / 90 °C
Aluminum ampacity—
Largest breaker15 A (240.4(D))

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 14 AWG can run

One-way distance at 3% and 5% drop.

Load120 V, 3%240 V, 3%120 V, 5%240 V, 5%
4 A143 ft286 ft238 ft477 ft
8 A71 ft143 ft119 ft238 ft
12 A47 ft95 ft79 ft159 ft
15 A38 ft76 ft63 ft127 ft

Copper, single-phase.

What 14 AWG is used for

14 AWG copper is the usual choice for 15 A lighting and receptacle circuits. In NM-B cable it is limited to the 60 °C rating, 15 A. Neighboring sizes: 12 AWG.

Common questions

How many amps can 14 AWG carry?

15 A at 60 °C, 20 A at 75 °C and 25 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C. The breaker is still limited to 15 A by 240.4(D).

What is the diameter of 14 AWG?

0.0641 in (1.63 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)