300 kcmil wire

300 kcmil copper carries 285 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

300 kcmil specifications

PropertyValue
Diameter, solid0.5477 in (13.91 mm)
Area300,000 cmil (152.01 mm²)
Resistance, copper0.0429 Ω per 1,000 ft
Resistance, aluminum0.0707 Ω per 1,000 ft
Copper ampacity240 / 285 / 320 A at 60 / 75 / 90 °C
Aluminum ampacity195 / 230 / 260 A
Largest breaker250 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 300 kcmil can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
62 A1,353 ft2,255 ft
125 A671 ft1,118 ft
200 A419 ft699 ft
250 A335 ft559 ft

Copper, single-phase.

What 300 kcmil is used for

300 kcmil copper is the usual choice for 250 to 285 A feeders. Neighboring sizes: 250 kcmil, 350 kcmil.

Common questions

How many amps can 300 kcmil carry?

240 A at 60 °C, 285 A at 75 °C and 320 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 300 kcmil?

0.5477 in (13.91 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)