350 kcmil wire

350 kcmil copper carries 310 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

350 kcmil specifications

PropertyValue
Diameter, solid0.5916 in (15.03 mm)
Area350,000 cmil (177.34 mm²)
Resistance, copper0.0367 Ω per 1,000 ft
Resistance, aluminum0.0605 Ω per 1,000 ft
Copper ampacity260 / 310 / 350 A at 60 / 75 / 90 °C
Aluminum ampacity210 / 250 / 280 A
Largest breaker300 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 350 kcmil can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
75 A1,307 ft2,179 ft
150 A653 ft1,089 ft
240 A408 ft681 ft
300 A326 ft544 ft

Copper, single-phase.

What 350 kcmil is used for

350 kcmil copper is the usual choice for 300 to 310 A feeders and services. Neighboring sizes: 300 kcmil, 400 kcmil.

Common questions

How many amps can 350 kcmil carry?

260 A at 60 °C, 310 A at 75 °C and 350 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 350 kcmil?

0.5916 in (15.03 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.