350 kcmil wire
350 kcmil copper carries 310 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
350 kcmil specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.5916 in (15.03 mm) |
| Area | 350,000 cmil (177.34 mm²) |
| Resistance, copper | 0.0367 Ω per 1,000 ft |
| Resistance, aluminum | 0.0605 Ω per 1,000 ft |
| Copper ampacity | 260 / 310 / 350 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 210 / 250 / 280 A |
| Largest breaker | 300 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 350 kcmil can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 75 A | 1,307 ft | 2,179 ft |
| 150 A | 653 ft | 1,089 ft |
| 240 A | 408 ft | 681 ft |
| 300 A | 326 ft | 544 ft |
Copper, single-phase.
Common questions
How many amps can 350 kcmil carry?
260 A at 60 °C, 310 A at 75 °C and 350 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 350 kcmil?
0.5916 in (15.03 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.