400 kcmil wire
400 kcmil copper carries 335 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
400 kcmil specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.6325 in (16.06 mm) |
| Area | 400,000 cmil (202.68 mm²) |
| Resistance, copper | 0.0321 Ω per 1,000 ft |
| Resistance, aluminum | 0.0529 Ω per 1,000 ft |
| Copper ampacity | 280 / 335 / 380 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 225 / 270 / 305 A |
| Largest breaker | 300 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 400 kcmil can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 75 A | 1,495 ft | 2,492 ft |
| 150 A | 747 ft | 1,246 ft |
| 240 A | 467 ft | 778 ft |
| 300 A | 373 ft | 623 ft |
Copper, single-phase.
Common questions
How many amps can 400 kcmil carry?
280 A at 60 °C, 335 A at 75 °C and 380 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 400 kcmil?
0.6325 in (16.06 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)