400 kcmil wire

400 kcmil copper carries 335 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

400 kcmil specifications

PropertyValue
Diameter, solid0.6325 in (16.06 mm)
Area400,000 cmil (202.68 mm²)
Resistance, copper0.0321 Ω per 1,000 ft
Resistance, aluminum0.0529 Ω per 1,000 ft
Copper ampacity280 / 335 / 380 A at 60 / 75 / 90 °C
Aluminum ampacity225 / 270 / 305 A
Largest breaker300 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 400 kcmil can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
75 A1,495 ft2,492 ft
150 A747 ft1,246 ft
240 A467 ft778 ft
300 A373 ft623 ft

Copper, single-phase.

What 400 kcmil is used for

400 kcmil copper is the usual choice for 335 A feeders and 400 A dwelling services in copper. Neighboring sizes: 350 kcmil, 500 kcmil.

Common questions

How many amps can 400 kcmil carry?

280 A at 60 °C, 335 A at 75 °C and 380 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 400 kcmil?

0.6325 in (16.06 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)