500 kcmil wire

500 kcmil copper carries 380 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

500 kcmil specifications

PropertyValue
Diameter, solid0.7071 in (17.96 mm)
Area500,000 cmil (253.35 mm²)
Resistance, copper0.0258 Ω per 1,000 ft
Resistance, aluminum0.0424 Ω per 1,000 ft
Copper ampacity320 / 380 / 430 A at 60 / 75 / 90 °C
Aluminum ampacity260 / 310 / 350 A
Largest breaker350 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 500 kcmil can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
88 A1,585 ft2,642 ft
175 A797 ft1,328 ft
280 A498 ft830 ft
350 A398 ft664 ft

Copper, single-phase.

What 500 kcmil is used for

500 kcmil copper is the usual choice for 380 A feeders and 400 A services. Neighboring sizes: 400 kcmil, 600 kcmil.

Common questions

How many amps can 500 kcmil carry?

320 A at 60 °C, 380 A at 75 °C and 430 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 500 kcmil?

0.7071 in (17.96 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.