Voltage Drop Calculator

HomeWire sizeWire gauge

600 kcmil wire

600 kcmil copper carries 420 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

600 kcmil specifications

PropertyValue
Diameter, solid0.7746 in (19.67 mm)
Area600,000 cmil (304.02 mm²)
Resistance, copper0.0214 Ω per 1,000 ft
Resistance, aluminum0.0353 Ω per 1,000 ft
Copper ampacity350 / 420 / 475 A at 60 / 75 / 90 °C
Aluminum ampacity285 / 340 / 385 A
Largest breaker400 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 600 kcmil can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
100 A1,682 ft2,803 ft
200 A841 ft1,401 ft
320 A525 ft876 ft
400 A420 ft700 ft

Copper, single-phase.

What 600 kcmil is used for

600 kcmil copper is the usual choice for 400 to 420 A feeders and 400 A aluminum dwelling services. Neighboring sizes: 500 kcmil, 750 kcmil.

Common questions

How many amps can 600 kcmil carry?

350 A at 60 °C, 420 A at 75 °C and 475 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 600 kcmil?

0.7746 in (19.67 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.