750 kcmil wire
750 kcmil copper carries 475 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
750 kcmil specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.8660 in (22.00 mm) |
| Area | 750,000 cmil (380.03 mm²) |
| Resistance, copper | 0.0171 Ω per 1,000 ft |
| Resistance, aluminum | 0.0282 Ω per 1,000 ft |
| Copper ampacity | 400 / 475 / 535 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 320 / 385 / 435 A |
| Largest breaker | 450 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 750 kcmil can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 112 A | 1,879 ft | 3,132 ft |
| 225 A | 935 ft | 1,559 ft |
| 360 A | 584 ft | 974 ft |
| 450 A | 467 ft | 779 ft |
Copper, single-phase.
What 750 kcmil is used for
750 kcmil copper is the usual choice for 475 A feeders and large commercial services. Neighboring sizes: 600 kcmil.
Common questions
How many amps can 750 kcmil carry?
400 A at 60 °C, 475 A at 75 °C and 535 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 750 kcmil?
0.8660 in (22.00 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)