Wire resistance calculator
Enter the gauge, length and conductor temperature to get the resistance in ohms.
Resistance
Fill in the circuit, then press the button.
Resistance table
| Size | Cu Ω/1,000 ft | Cu Ω/ft | Al Ω/1,000 ft |
|---|---|---|---|
| 18 AWG | 7.95 | 0.007950 | — |
| 16 AWG | 4.99 | 0.004990 | — |
| 14 AWG | 3.14 | 0.003140 | — |
| 12 AWG | 1.98 | 0.001980 | 3.25 |
| 10 AWG | 1.24 | 0.001240 | 2.04 |
| 8 AWG | 0.778 | 0.000778 | 1.28 |
| 6 AWG | 0.491 | 0.000491 | 0.808 |
| 4 AWG | 0.308 | 0.000308 | 0.508 |
| 3 AWG | 0.245 | 0.000245 | 0.403 |
| 2 AWG | 0.194 | 0.000194 | 0.319 |
| 1 AWG | 0.154 | 0.000154 | 0.253 |
| 1/0 AWG | 0.122 | 0.000122 | 0.201 |
| 2/0 AWG | 0.0967 | 0.000097 | 0.159 |
| 3/0 AWG | 0.0766 | 0.000077 | 0.126 |
| 4/0 AWG | 0.0608 | 0.000061 | 0.1 |
| 250 kcmil | 0.0515 | 0.000051 | 0.0847 |
| 300 kcmil | 0.0429 | 0.000043 | 0.0707 |
| 350 kcmil | 0.0367 | 0.000037 | 0.0605 |
| 400 kcmil | 0.0321 | 0.000032 | 0.0529 |
| 500 kcmil | 0.0258 | 0.000026 | 0.0424 |
| 600 kcmil | 0.0214 | 0.000021 | 0.0353 |
| 750 kcmil | 0.0171 | 0.000017 | 0.0282 |
NEC Chapter 9, Table 8, stranded, uncoated copper, 75 °C.
Temperature correction
R₂ = R₁ × [1 + α × (T₂ − 75)]
α is 0.00323 for copper and 0.00330 for aluminum, the coefficients in the notes to Table 8. At 20 °C copper is about 18% lower than the table value.
Common questions
What is the resistance of 12 gauge wire per foot?
About 0.00198 Ω per foot at 75 °C for stranded copper, or 0.00162 Ω at 20 °C.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)