18 AWG wire
18 AWG is too small for building branch circuits. It is used for doorbells, thermostats, low-voltage lighting leads and lamp cords. On low-voltage DC runs, voltage drop limits it long before heat does.
Voltage drop
Fill in the circuit, then press the button.
18 AWG specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.0402 in (1.02 mm) |
| Area | 1,620 cmil (0.821 mm²) |
| Resistance | 7.95 Ω per 1,000 ft at 75 °C |
| Fixture wire ampacity | 6 A (NEC Table 402.5) |
Maximum one-way distance, 3% drop
| Current | 12 V | 24 V |
|---|---|---|
| 0.5 A | 45 ft | 90 ft |
| 1 A | 22 ft | 45 ft |
| 2 A | 11 ft | 22 ft |
| 3 A | 7 ft | 15 ft |
| 5 A | 4 ft | 9 ft |
Class 2 power supplies limit the current so that these small wires stay safe; voltage drop is the main design check.
Common questions
How many amps can 18 gauge wire carry?
As fixture wire, 6 A under NEC Table 402.5. Cords and appliance leads have their own ratings in Article 400.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)