18 AWG wire

18 AWG is too small for building branch circuits. It is used for doorbells, thermostats, low-voltage lighting leads and lamp cords. On low-voltage DC runs, voltage drop limits it long before heat does.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

18 AWG specifications

PropertyValue
Diameter, solid0.0402 in (1.02 mm)
Area1,620 cmil (0.821 mm²)
Resistance7.95 Ω per 1,000 ft at 75 °C
Fixture wire ampacity6 A (NEC Table 402.5)

Maximum one-way distance, 3% drop

Current12 V24 V
0.5 A45 ft90 ft
1 A22 ft45 ft
2 A11 ft22 ft
3 A7 ft15 ft
5 A4 ft9 ft

Class 2 power supplies limit the current so that these small wires stay safe; voltage drop is the main design check.

Common questions

How many amps can 18 gauge wire carry?

As fixture wire, 6 A under NEC Table 402.5. Cords and appliance leads have their own ratings in Article 400.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)