Welder wire size calculator
Welders run in bursts, so the NEC lets you size the wire from the duty cycle. Enter I1max and the duty cycle from the nameplate.
Welder circuit
Fill in the circuit, then press the button.
Duty cycle multipliers (Table 630.11(A))
| Duty cycle | Multiplier |
|---|---|
| 100% | 1.0 |
| 90% | 0.95 |
| 80% | 0.89 |
| 70% | 0.84 |
| 60% | 0.78 |
| 50% | 0.71 |
| 40% | 0.63 |
| 30% | 0.55 |
| 20 or less% | 0.45 |
Example
A welder with I1max of 48 A at 30% duty cycle: 48 × 0.55 = 26.4 A, so 10 AWG copper. The breaker may be up to 200% of 48 A, a 90 A breaker, though most manuals call for 50 A.
Common questions
Why can the breaker be larger than the wire?
Welders draw high current in short bursts. Article 630 allows a breaker up to 200% of I1max to avoid nuisance trips, while the wire is sized on the averaged load.