Welder wire size calculator

Welders run in bursts, so the NEC lets you size the wire from the duty cycle. Enter I1max and the duty cycle from the nameplate.

A
Enter 0 to skip voltage drop.
V

Welder circuit

Fill in the circuit, then press the button.

Duty cycle multipliers (Table 630.11(A))

Duty cycleMultiplier
100%1.0
90%0.95
80%0.89
70%0.84
60%0.78
50%0.71
40%0.63
30%0.55
20 or less%0.45

Example

A welder with I1max of 48 A at 30% duty cycle: 48 × 0.55 = 26.4 A, so 10 AWG copper. The breaker may be up to 200% of 48 A, a 90 A breaker, though most manuals call for 50 A.

Common questions

Why can the breaker be larger than the wire?

Welders draw high current in short bursts. Article 630 allows a breaker up to 200% of I1max to avoid nuisance trips, while the wire is sized on the averaged load.