100 amp service wire size

A 100 A single-family service may use 4 AWG copper or 2 AWG aluminum under NEC 310.12. Long underground laterals and feeders that serve only part of the building need more.

One way. Enter 0 to skip voltage drop.
V
%

Service conductors

Fill in the circuit, then press the button.

100 A conductor sizes

UseCopperAluminumBasis
Whole-dwelling service or main feeder4 AWG2 AWGTable 310.12 (83% of rating)
Feeder to part of the building3 AWG1 AWGTable 310.16, 75 °C
Grounding electrode conductor8 AWG6 AWGTable 250.66, based on the aluminum size

Table 310.12 lets a one-family dwelling service be sized at 83% of its rating because the whole house never draws its full rating for long. It applies only where the conductors carry the entire dwelling load, and only for 120/240 V single-phase services. Correction factors for heat, such as conductors in a hot attic or on a sunny roof, still apply.

Voltage drop on a 100 A service

At 83% of rating (83 A), single-phase 240 V:

One-way length2 AWG Al4 AWG Cu
50 ft2.6 V (1.1%)2.6 V (1.1%)
100 ft5.3 V (2.2%)5.1 V (2.1%)
150 ft7.9 V (3.3%)7.7 V (3.2%)
200 ft10.6 V (4.4%)10.2 V (4.3%)
300 ft15.9 V (6.6%)15.3 V (6.4%)

Most utilities own the drop or lateral to the meter; this applies to conductors you install. Meter-to-house runs over about 150 ft often go one or two sizes larger.

Cable choices

  • SER (4 conductors) or SEU (3 conductors) for overhead service entrance runs.
  • URD / USE-2 aluminum triplex or quadruplex for direct-burial laterals, 24 in deep under Table 300.5.
  • XHHW-2 or THWN-2 in conduit.

The neutral may be smaller than the hots when the calculated neutral load allows (220.61), but not smaller than the grounding electrode conductor (250.24(C)).

Common questions

Can I use 2 AWG aluminum for a 100 amp service?

Yes, for a single-family dwelling service under 310.12. For a 100 A feeder that is not the main service, use 1 AWG aluminum.

Does 310.12 apply to a subpanel?

Only if that panel is fed by conductors carrying the entire dwelling load, such as a main disconnect outside feeding the interior panel. A garage or shop subpanel uses Table 310.16.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)