NEMA 14-50 outlet wire size
A 14-50 receptacle is rated 50 A and needs 6 AWG copper NM-B, or 8 AWG THHN in conduit with 75 °C terminals. EV charging at 40 A counts as continuous.
Circuit
Fill in the circuit, then press the button.
14-50 circuit
| Part | Size |
|---|---|
| Breaker | 50 A 2-pole (GFCI for EV and many outdoor uses) |
| NM-B | 6/3 with ground |
| THHN/THWN-2 in conduit | 8 AWG at 75 °C, 6 AWG for long runs |
| Aluminum | 6 AWG at 75 °C (50 A) |
Maximum distance at 40 A, 240 V, 3%
| Wire | Max |
|---|---|
| 8 AWG | 115 ft |
| 6 AWG | 183 ft |
| 4 AWG | 292 ft |
Common questions
Does a 14-50 for EV charging need GFCI?
Yes. NEC 210.8(F) and 625.54 require GFCI protection for receptacles that supply EV chargers.