NEMA 14-50 outlet wire size

A 14-50 receptacle is rated 50 A and needs 6 AWG copper NM-B, or 8 AWG THHN in conduit with 75 °C terminals. EV charging at 40 A counts as continuous.

V
One way from the panel. Enter 0 to skip voltage drop.
%

Circuit

Fill in the circuit, then press the button.

14-50 circuit

PartSize
Breaker50 A 2-pole (GFCI for EV and many outdoor uses)
NM-B6/3 with ground
THHN/THWN-2 in conduit8 AWG at 75 °C, 6 AWG for long runs
Aluminum6 AWG at 75 °C (50 A)

Maximum distance at 40 A, 240 V, 3%

WireMax
8 AWG115 ft
6 AWG183 ft
4 AWG292 ft

Common questions

Does a 14-50 for EV charging need GFCI?

Yes. NEC 210.8(F) and 625.54 require GFCI protection for receptacles that supply EV chargers.