50 amp range wire size
Ranges are sized from the nameplate kW using the NEC demand factors, which usually lands on a 50 A circuit for larger ranges.
Range circuit
Fill in the circuit, then press the button.
50 A range circuit
| Part | Size |
|---|---|
| Breaker | 50 A 2-pole |
| NM-B (60 °C) | 6 AWG/3 with ground |
| THHN copper (75 °C) | 8 AWG |
| Aluminum SER (75 °C) | 6 AWG |
| Receptacle | NEMA 14-50R |
Range demand (NEC 220.55)
| Nameplate | Demand | Amps at 240 V | Circuit |
|---|---|---|---|
| 8.75 kW or less | 8 kW (Column C) | 33 A | 40 A |
| 12 kW | 8 kW | 33 A | 40 A |
| 14 kW | 8.8 kW (+5% per kW over 12) | 37 A | 40 A |
| 16 kW | 9.6 kW | 40 A | 40–50 A |
Column C applies to one range up to 12 kW; each kW above 12 adds 5% to the 8 kW figure (Note 1). Many installers use 50 A for large ranges anyway, as the instructions often call for it.
Common questions
Can I use 8/3 for a 50 A range?
With THHN in conduit at 75 °C, 8 AWG is rated 50 A. In NM-B (60 °C) it is only 40 A, so 50 A needs 6/3 NM-B.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)