50 amp range wire size

Ranges are sized from the nameplate kW using the NEC demand factors, which usually lands on a 50 A circuit for larger ranges.

V
One way from the panel. Enter 0 to skip voltage drop.
%

Range circuit

Fill in the circuit, then press the button.

50 A range circuit

PartSize
Breaker50 A 2-pole
NM-B (60 °C)6 AWG/3 with ground
THHN copper (75 °C)8 AWG
Aluminum SER (75 °C)6 AWG
ReceptacleNEMA 14-50R

Range demand (NEC 220.55)

NameplateDemandAmps at 240 VCircuit
8.75 kW or less8 kW (Column C)33 A40 A
12 kW8 kW33 A40 A
14 kW8.8 kW (+5% per kW over 12)37 A40 A
16 kW9.6 kW40 A40–50 A

Column C applies to one range up to 12 kW; each kW above 12 adds 5% to the 8 kW figure (Note 1). Many installers use 50 A for large ranges anyway, as the instructions often call for it.

Common questions

Can I use 8/3 for a 50 A range?

With THHN in conduit at 75 °C, 8 AWG is rated 50 A. In NM-B (60 °C) it is only 40 A, so 50 A needs 6/3 NM-B.