50 amp RV outlet wire size
A 50 A RV hookup is 120/240 V with two hots, neutral and ground on a NEMA 14-50 receptacle. Each hot can carry 50 A at 120 V.
Wire size
Fill in the circuit, then press the button.
Wire by distance at 40 A
| Wire | 3% max at 240 V | 3% max, 120 V leg |
|---|---|---|
| 6 AWG | 183 ft | 91 ft |
| 4 AWG | 292 ft | 146 ft |
| 2 AWG | 463 ft | 231 ft |
Because most RV loads are 120 V, figure the drop on the 120 V leg for the realistic case.
Parts list
- 50 A 2-pole breaker
- 6 AWG copper THWN-2, or 6/3 with ground NM-B indoors only up to 55 A
- NEMA 14-50R in a weatherproof RV box
Common questions
Is a 50 A RV outlet the same as an EV 14-50?
Same receptacle. For EV use, the charger must be set to 40 A or less on a 50 A circuit.