Shed and detached garage wire size

A single 20 A circuit covers lights and a few tools. A subpanel lets you run a heater, compressor or welder. Enter the feeder you plan and the distance.

V
A
One way, from the source to the load.
%

Feeder size

Fill in the circuit, then press the button.

Common choices

FeedUp to 50 ft100 ft150 ft200 ft
20 A, 120 V12 AWG8 AWG6 AWG6 AWG
30 A, 240 V10 AWG10 AWG8 AWG6 AWG
60 A, 240 V6 AWG6 AWG6 AWG4 AWG
100 A, 240 V3 AWG3 AWG3 AWG2 AWG

Copper, 3% drop at 80% load, 60 °C column for UF or NM-B.

Rules for outbuildings

  • One circuit or one feeder per building (225.30).
  • A disconnect at the building (225.31).
  • A grounding electrode at the building when fed by a feeder or more than one circuit (250.32).
  • Buried at Table 300.5 depths.

Common questions

Can I run a single circuit to a shed?

Yes. One 120 V or 240 V circuit, or one multiwire circuit, is allowed. The switch or breaker at the shed serves as its disconnect.