Shed and detached garage wire size
A single 20 A circuit covers lights and a few tools. A subpanel lets you run a heater, compressor or welder. Enter the feeder you plan and the distance.
Feeder size
Fill in the circuit, then press the button.
Common choices
| Feed | Up to 50 ft | 100 ft | 150 ft | 200 ft |
|---|---|---|---|---|
| 20 A, 120 V | 12 AWG | 8 AWG | 6 AWG | 6 AWG |
| 30 A, 240 V | 10 AWG | 10 AWG | 8 AWG | 6 AWG |
| 60 A, 240 V | 6 AWG | 6 AWG | 6 AWG | 4 AWG |
| 100 A, 240 V | 3 AWG | 3 AWG | 3 AWG | 2 AWG |
Copper, 3% drop at 80% load, 60 °C column for UF or NM-B.
Rules for outbuildings
- One circuit or one feeder per building (225.30).
- A disconnect at the building (225.31).
- A grounding electrode at the building when fed by a feeder or more than one circuit (250.32).
- Buried at Table 300.5 depths.
Common questions
Can I run a single circuit to a shed?
Yes. One 120 V or 240 V circuit, or one multiwire circuit, is allowed. The switch or breaker at the shed serves as its disconnect.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)