Air compressor wire size

Compressor motors start under load and draw several times their running current, so voltage drop matters more than for most loads. Pick the horsepower and run.

One way from the panel to the motor. Enter 0 to skip voltage drop.
%
Used for voltage drop. Leave blank to use the NEC table current.
A

Compressor circuit

Fill in the circuit, then press the button.

Single-phase compressors

HPFLC at 230 VWire (125%)Max breaker
1 HP8 A14 AWG20 A
1-1/2 HP10 A14 AWG25 A
2 HP12 A14 AWG30 A
3 HP17 A10 AWG45 A
5 HP28 A8 AWG70 A
7-1/2 HP40 A8 AWG100 A

Use true motor horsepower. Some consumer compressors are labeled with "peak" HP several times the running rating; go by the nameplate amps.

Extension cords

Compressor makers generally say to use more air hose rather than a longer cord, since a cord adds voltage drop on top of the branch circuit.

Common questions

What breaker for a 5 HP compressor at 240 V?

The table current is 28 A, so 10 AWG copper. The maximum inverse-time breaker is 250% = 70 A; most compressor manuals specify 40 A.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)