Cooktop wire size
Electric and induction cooktops usually need 40 or 50 A at 240 V. Enter the nameplate rating.
Circuit
Fill in the circuit, then press the button.
By nameplate kW at 240 V
| Nameplate | Amps | Breaker | Copper (60 °C) | Copper (75 °C) |
|---|---|---|---|---|
| 6.0 kW | 25.0 A | 25 A | 10 AWG | 10 AWG |
| 7.2 kW | 30.0 A | 30 A | 10 AWG | 10 AWG |
| 8.4 kW | 35.0 A | 35 A | 8 AWG | 8 AWG |
| 9.6 kW | 40.0 A | 40 A | 8 AWG | 8 AWG |
| 11.0 kW | 45.8 A | 50 A | 6 AWG | 8 AWG |
Demand factors
For the branch circuit, NEC 210.19(A)(3) lets a single wall oven or cooktop use its nameplate rating; for a counter-mounted cooktop and up to two wall ovens on one circuit, add their nameplates and treat them as one range under 220.55. Installation manuals usually name the exact breaker; use it.
Common questions
What size wire for a cooktop on a 40 A breaker?
8 AWG copper in NM-B or 8 AWG THHN with 75 °C terminals.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)