15 kW electric furnace wire size
15 kW at 240 V is 62.5 A. Fixed electric heat is sized at 125%, and heating elements over 48 A must be split into circuits of 48 A or less (424.22(B)).
Furnace circuit
Fill in the circuit, then press the button.
15 kW furnace
| Circuits | kW each | Amps | Breaker (125%) | Copper (75 °C) |
|---|---|---|---|---|
| 2 | 7.5 | 31.2 A | 40 A | 8 AWG |
| 3 | 5.0 | 20.8 A | 30 A | 10 AWG |
Add the blower motor current from the nameplate if the unit lists a single MCA; most air handlers list MCA and MOCP for each circuit.
Common questions
What breaker does a 15 kW furnace need?
As 2 circuits, 40 A each. The unit label lists the MOCP for each circuit; use it.