15 kW electric furnace wire size

15 kW at 240 V is 62.5 A. Fixed electric heat is sized at 125%, and heating elements over 48 A must be split into circuits of 48 A or less (424.22(B)).

V
One way from the panel. Enter 0 to skip voltage drop.
%

Furnace circuit

Fill in the circuit, then press the button.

15 kW furnace

CircuitskW eachAmpsBreaker (125%)Copper (75 °C)
27.531.2 A40 A8 AWG
35.020.8 A30 A10 AWG

Add the blower motor current from the nameplate if the unit lists a single MCA; most air handlers list MCA and MOCP for each circuit.

Common questions

What breaker does a 15 kW furnace need?

As 2 circuits, 40 A each. The unit label lists the MOCP for each circuit; use it.