20 kW electric furnace wire size
20 kW at 240 V is 83.3 A. Fixed electric heat is sized at 125%, and heating elements over 48 A must be split into circuits of 48 A or less (424.22(B)).
Furnace circuit
Fill in the circuit, then press the button.
20 kW furnace
| Circuits | kW each | Amps | Breaker (125%) | Copper (75 °C) |
|---|---|---|---|---|
| 2 | 10.0 | 41.7 A | 60 A | 6 AWG |
| 3 | 6.7 | 27.8 A | 35 A | 8 AWG |
Add the blower motor current from the nameplate if the unit lists a single MCA; most air handlers list MCA and MOCP for each circuit.
Common questions
What breaker does a 20 kW furnace need?
As 2 circuits, 60 A each. The unit label lists the MOCP for each circuit; use it.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)