26 kW generator wire size
At its 26 kW rating a 240 V generator delivers about 108 A. NEC 445.13 sizes the conductors from the generator to the first protection at 115% of nameplate current: 125 A.
Generator feeder
Fill in the circuit, then press the button.
26 kW generator conductors
| Material | Size at 75 °C | 3% max distance |
|---|---|---|
| Copper | 1 AWG | 215 ft |
| Aluminum | 2/0 AWG | 208 ft |
If the generator's built-in breaker is smaller than 115% of its rating, the conductors may be sized to the breaker instead. Check the installation manual, which also lists the maximum distance per wire size.
Common questions
Natural gas or propane rating?
Use the higher of the two ratings for wire sizing. Many standby units are rated a few kW lower on natural gas.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)