26 kW generator wire size

At its 26 kW rating a 240 V generator delivers about 108 A. NEC 445.13 sizes the conductors from the generator to the first protection at 115% of nameplate current: 125 A.

V
One way from the panel. Enter 0 to skip voltage drop.
%

Generator feeder

Fill in the circuit, then press the button.

26 kW generator conductors

MaterialSize at 75 °C3% max distance
Copper1 AWG215 ft
Aluminum2/0 AWG208 ft

If the generator's built-in breaker is smaller than 115% of its rating, the conductors may be sized to the breaker instead. Check the installation manual, which also lists the maximum distance per wire size.

Common questions

Natural gas or propane rating?

Use the higher of the two ratings for wire sizing. Many standby units are rated a few kW lower on natural gas.