Aluminum vs copper wire
Run the same circuit twice, once in each metal, to compare. The tables below show the size difference for ampacity and for voltage drop.
Wire size
Fill in the circuit, then press the button.
Side by side
| Property | Copper | Aluminum |
|---|---|---|
| Conductivity | 100% IACS | about 61% IACS |
| Weight for equal ampacity | about 2× | 1× |
| Resistance, 4/0 | 0.0608 Ω/kft | 0.1 Ω/kft |
| Ampacity, 4/0 at 75 °C | 230 A | 180 A |
| Branch circuits | standard | needs CO/ALR devices |
Equivalent sizes
| Copper | Al for equal ampacity (75 °C) | Al for equal voltage drop |
|---|---|---|
| 8 AWG | 6 AWG | 4 AWG |
| 6 AWG | 4 AWG | 3 AWG |
| 4 AWG | 2 AWG | 1 AWG |
| 2 AWG | 1/0 AWG | 2/0 AWG |
| 1/0 AWG | 3/0 AWG | 4/0 AWG |
| 2/0 AWG | 4/0 AWG | 250 kcmil |
| 3/0 AWG | 250 kcmil | 300 kcmil |
| 4/0 AWG | 300 kcmil | 350 kcmil |
| 250 kcmil | 400 kcmil | 500 kcmil |
| 350 kcmil | 500 kcmil | 600 kcmil |
Common questions
Is aluminum wire cheaper?
Per amp of capacity, aluminum feeder cable usually costs well under half of copper. Most utility and many residential service conductors are aluminum for that reason.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)