Voltage Drop Calculator

HomeWire sizeWire gauge

Aluminum wire size chart

Aluminum feeders and service cable cost less than copper but need larger sizes. Enter the amps to get the aluminum size.

A

Aluminum size

Fill in the circuit, then press the button.

Aluminum ampacity

Size60 °C75 °C90 °C
12 AWG15 A20 A25 A
10 AWG25 A30 A35 A
8 AWG35 A40 A45 A
6 AWG40 A50 A55 A
4 AWG55 A65 A75 A
3 AWG65 A75 A85 A
2 AWG75 A90 A100 A
1 AWG85 A100 A115 A
1/0 AWG100 A120 A135 A
2/0 AWG115 A135 A150 A
3/0 AWG130 A155 A175 A
4/0 AWG150 A180 A205 A
250 kcmil170 A205 A230 A
300 kcmil195 A230 A260 A
350 kcmil210 A250 A280 A
400 kcmil225 A270 A305 A
500 kcmil260 A310 A350 A
600 kcmil285 A340 A385 A
750 kcmil320 A385 A435 A

Copper to aluminum swaps at 75 °C

AmpsCopperAluminum
30 A10 AWG8 AWG
40 A8 AWG8 AWG
50 A8 AWG6 AWG
60 A6 AWG4 AWG
100 A3 AWG1 AWG
125 A1 AWG2/0 AWG
150 A1/0 AWG3/0 AWG
200 A3/0 AWG250 kcmil
225 A4/0 AWG300 kcmil
300 A350 kcmil500 kcmil
400 A600 kcmilNone AWG

Common questions

Why is aluminum allowed for 200 A services at 4/0?

4/0 aluminum is rated 180 A at 75 °C. A one-family dwelling service only has to be sized for 83% of its rating under 310.12, which is 166 A for 200 A service.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)