Romex NM-B wire size
NM-B cable has 90 °C insulation, but NEC 334.80 limits its ampacity to the 60 °C column. Enter the breaker size to get the cable you need.
NM-B size
Fill in the circuit, then press the button.
NM-B ampacity
| Cable | Ampacity (60 °C) | Typical breaker | Common use |
|---|---|---|---|
| 14/2 or 14/3 | 15 A | 15 A | lighting, 15 A outlets |
| 12/2 or 12/3 | 20 A | 20 A | 20 A outlets |
| 10/2 or 10/3 | 30 A | 30 A | dryer, water heater |
| 8/2 or 8/3 | 40 A | 40 A | 40 A range or cooktop |
| 6/2 or 6/3 | 55 A | 50 A | 50–55 A range, subpanel |
| 4/2 or 4/3 | 70 A | 70 A | 70 A subpanel |
| 2/2 or 2/3 | 95 A | 90 A | 90 A subpanel |
Color codes
- White jacket: 14 AWG
- Yellow: 12 AWG
- Orange: 10 AWG
- Black: 8 and 6 AWG
- Gray: UF-B underground cable
The colors are a manufacturer convention, not a code rule; read the printing on the jacket.
Common questions
Can 6/3 Romex handle 60 amps?
No. 6 AWG NM-B is rated 55 A at 60 °C. The next standard breaker above 55 A is 60 A, which 240.4(B) allows only for noncontinuous loads on circuits that are not multioutlet receptacle circuits. For a 60 A continuous load, use 4 AWG.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)