THHN wire ampacity
THHN is rated 90 °C dry, and THWN-2 90 °C wet, so you can derate from the 90 °C column. The result is still capped at the 75 °C terminal rating.
Adjusted ampacity
Fill in the circuit, then press the button.
THHN/THWN-2 copper
| Size | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| 14 AWG | 15 A | 20 A | 25 A |
| 12 AWG | 20 A | 25 A | 30 A |
| 10 AWG | 30 A | 35 A | 40 A |
| 8 AWG | 40 A | 50 A | 55 A |
| 6 AWG | 55 A | 65 A | 75 A |
| 4 AWG | 70 A | 85 A | 95 A |
| 3 AWG | 85 A | 100 A | 115 A |
| 2 AWG | 95 A | 115 A | 130 A |
| 1 AWG | 110 A | 130 A | 145 A |
| 1/0 AWG | 125 A | 150 A | 170 A |
| 2/0 AWG | 145 A | 175 A | 195 A |
| 3/0 AWG | 165 A | 200 A | 225 A |
| 4/0 AWG | 195 A | 230 A | 260 A |
| 250 kcmil | 215 A | 255 A | 290 A |
| 300 kcmil | 240 A | 285 A | 320 A |
| 350 kcmil | 260 A | 310 A | 350 A |
Why derate from 90 °C?
With six current-carrying 10 AWG THHN in one conduit, the 90 °C ampacity of 40 A × 80% = 32 A. That still exceeds 30 A, so 10 AWG stays on a 30 A breaker. Starting from 75 °C (35 A × 80% = 28 A) would force a smaller breaker or larger wire.
Common questions
Is THHN rated for wet locations?
Plain THHN is dry and damp only. Most wire sold today is dual-rated THHN/THWN-2, which is 90 °C in wet locations such as underground conduit.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)