UF cable size
UF-B can be buried directly in the ground. Like NM-B it uses the 60 °C column. Long runs to sheds and outbuildings often need one size up for voltage drop.
UF cable size
Fill in the circuit, then press the button.
UF-B ampacity
| Size | 60 °C ampacity | Breaker |
|---|---|---|
| 14 AWG | 15 A | 15 A |
| 12 AWG | 20 A | 20 A |
| 10 AWG | 30 A | 30 A |
| 8 AWG | 40 A | 40 A |
| 6 AWG | 55 A | 50 A |
Burial depth
Direct-buried UF needs 24 in of cover in a yard. A 120 V, 20 A or smaller residential circuit with GFCI protection may be 12 in deep. Under a 4 in slab with no vehicle traffic, 18 in. See the burial depth calculator.
Common questions
Can UF cable be used indoors?
Yes, UF may be used anywhere NM is allowed, following NM installation rules (340.10).
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)