Voltage Drop Calculator

HomeWire sizeWire gauge

UF cable size

UF-B can be buried directly in the ground. Like NM-B it uses the 60 °C column. Long runs to sheds and outbuildings often need one size up for voltage drop.

V
A
One way, from the source to the load.
%

UF cable size

Fill in the circuit, then press the button.

UF-B ampacity

Size60 °C ampacityBreaker
14 AWG15 A15 A
12 AWG20 A20 A
10 AWG30 A30 A
8 AWG40 A40 A
6 AWG55 A50 A

Burial depth

Direct-buried UF needs 24 in of cover in a yard. A 120 V, 20 A or smaller residential circuit with GFCI protection may be 12 in deep. Under a 4 in slab with no vehicle traffic, 18 in. See the burial depth calculator.

Common questions

Can UF cable be used indoors?

Yes, UF may be used anywhere NM is allowed, following NM installation rules (340.10).

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)