Voltage Drop Calculator

HomeWire size

AWG wire gauge chart

Pick a size to see every number for it, or scan the full chart below. Each AWG step is about 26% more area; every six gauges doubles the diameter.

Wire data

Fill in the circuit, then press the button.

Full chart

SizeDiametermm²Cu Ω/kftCu amps 60/75/90 °C
18 AWG0.0402 in0.827.95—
16 AWG0.0508 in1.314.99—
14 AWG0.0641 in2.083.1415/20/25
12 AWG0.0808 in3.311.9820/25/30
10 AWG0.1019 in5.261.2430/35/40
8 AWG0.1285 in8.370.77840/50/55
6 AWG0.1620 in13.300.49155/65/75
4 AWG0.2043 in21.150.30870/85/95
3 AWG0.2294 in26.660.24585/100/115
2 AWG0.2576 in33.620.19495/115/130
1 AWG0.2893 in42.410.154110/130/145
1/0 AWG0.3250 in53.510.122125/150/170
2/0 AWG0.3648 in67.440.0967145/175/195
3/0 AWG0.4096 in85.020.0766165/200/225
4/0 AWG0.4600 in107.220.0608195/230/260
250 kcmil0.5000 in126.670.0515215/255/290
300 kcmil0.5477 in152.010.0429240/285/320
350 kcmil0.5916 in177.340.0367260/310/350
400 kcmil0.6325 in202.680.0321280/335/380
500 kcmil0.7071 in253.350.0258320/380/430
600 kcmil0.7746 in304.020.0214350/420/475
750 kcmil0.8660 in380.030.0171400/475/535

Diameter is for a solid conductor. Ampacity from NEC Table 310.16; resistance from Chapter 9, Table 8.

How AWG works

American Wire Gauge numbers run backward: a smaller number is a thicker wire. Past 1 AWG the sizes become 1/0, 2/0, 3/0 and 4/0 ("one aught" to "four aught"), then switch to kcmil, thousands of circular mils. The diameter of gauge n is 0.005 × 92^((36 − n) ÷ 39) inches (ASTM B258).

Common questions

Which is bigger, 10 gauge or 12 gauge?

10 gauge. Lower AWG numbers are thicker. 10 AWG has about 59% more copper area than 12 AWG.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • ASTM B258, Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires